THERMAL BUILDING SOLUTIONS
EN-RaychemQuickStatTCthermostat-IM-H5851710/14
2 / 6
Important: This thermostat must be installed according to all
relevant national and local electrical codes. The installation must
be performed by qualified personnel.
Locating the floor temperature sensor
The floor temperature sensor is installed under the floor surface.
See Section 6 of the appropriate system installation manual for more
details. Perform the Sensor Resistance Test prior to terminating
the floor sensor to the thermostat. See Section 7 of the appropriate
system installation manual for more details.
Wiring the thermostat
1. Remove the control module from the power base by loosening
the captive screw underneath the base.
2. Connect the floor heating cold
leads to the load wires (two
inner wires) using the supplied
wire nuts.
3. Connect the power supply
leads to the power base wires
(two outer wires) using the
supplied wire nuts.
4. Connect the floor heating cold
lead braid (ground) to the sup-
ply ground in the electrical
junction box.
5. Insert the floor sensor cable through one of the two openings
on the power base and connect to terminals 1 and 2 (no polar-
ity). Position the sensor cable such that it does not come in
contact with the floor heating wires.
6. Push the excess length of the wires back inside the electrical
junction box
7. Secure the power base to the electrical junction box using the
provided mounting screws
8. Verify the settings of the configuration switches on the back
of the control module. Default settings for the configuration
switches are highlighted below.
Important: If your system is installed underneath laminate
or engineered wood flooring, you MUST use AF mode with the
default settings. Note the factory default is AF mode.
No. Configuration Up Down
1 Display format °F/12 hr °C/24 hr
2 Early Start
1
Enable Disable
3 Temperature control mode
2
F AF
1
Early Start can be used in Automatic mode only. When this
function is enabled, the thermostat calculates the optimal time
to start heating in order to obtain the desired temperature by the
set time. The thermostat re-assesses the start time daily based
on the previous day’s results.
Note: If you wish to use only 2 periods, set periods “1 and 4”
or periods “2 and 3. Early Start will not work if you set periods
“1 and 2” or periods “3 and 4”.
2
To select floor sensing mode, place the switch to the F position.
To select floor sensing and ambient sensing mode, place the
switch to the AF position and ensure that the remote tempera-
ture sensor is connected to the thermostat. To select the A
mode, place the switch in the AF position and ensure that the
remote temperature sensor is NOT connected to the thermostat.
9. Install the control module onto the power base.
WARNING: Shock Hazard. Turn off the power to the circuit
at the main power panel to avoid electric shock.
WARNING: Shock Hazard. To prevent shock, the QuickNet
floor heating mat and CeraPro floor heating cable must be
connected to ground.
Control
module
Air
vents
Air
vents
Powe
r
base
Power
supply
Load / Floor heating mat
Supply
ground
Floor
heating
cold l
ead
ground
Floor temperature sensor
Supply
ground
Floor
heating
cold lead
ground
Installation